Laying and Fixing Procedures

Laying of Single Skin and Built Up Insulation Systems

The pitch of the roof should be chosen to maintain efficient rain water drainage. Care should be taken to avoid reducing the pitch to produce minimal drainage conditions which could produce 'ponding' or, with driving winds, negative drainage.

Where corrugated profiles are used we recommend the roof pitch should not be less than 10 degrees. Using trapezoidal profiles the pitch can be reduced to 6 degrees. Where shallower pitches are envisaged we recommend that technical advice should be taken at the design stage to ensure that all necessary precautions are taken.

Cutting

The following points should be observed if any profiled sheets have to be cut on site:

  • Burning through with oxyacetylene (or similar) torches is completely unacceptable. It is almost impossible to cut a clean line and the coating is invariably damaged.
  • Cutting with an abrasive disc is not recommended. It is not easy to get a clean line and the coating can be damaged by the heat generated or by a carelessly held disc.
  • Using a sheet nibbler is highly recommended. This gives a very clean edge and causes no damage. It is also easy to cut complex-shaped holes through the sheet.
  • Use of a reciprocating saw for on-site cutting of composite panels is recommended. 

It is also necessary to remove all swarf and other debris as roof erection proceeds since they can cause discolouration and corrosion.

Fixings

Apart from just attaching the sheets to the framework and supporting their self weight, the fixings have to withstand  considerable wind pressures and be weather-proof and durable. It is also important that the fixings are visually compatible with the cladding.

Probably the most popular fixings are the N.W.S.S. range of self-tapping / self-drilling screws. They are neat, strong and applied completely from the outer face of the cladding. They are available with colour coded, moulded heads or separate snap-on plastic caps in colours to match the cladding and incorparate a sealing washer under the head. A crown fixing with saddle washers is also possible.

End Laps, Use of Sealants and Side Lap Fasteners

Steel Sheet Fixing

   ROOF PITCH (Degrees) EXPOSURE
 SEVEREMODERATE
 End LapSide Lap
Fast Centres 
 End Lap Side Lap
Fast Centres 
 Over 15 150300 150450 
 10 - 15 150300 150450
 6 - 10 200300200450
WALLS150As Necessary100450
 NOTE: Side and End Lap Sealant on roof pitches below 15°, walls with severe exposure Side Lap Sealant required.

 

 